USER’S GUIDE
InRow RC ACRC100 Series
12
Main screen status fields.
•A Stat field reports the status of the InRow RC.
Stat : P+ N+ A+
InRow RC status field.
The Status field displays the status of the Cooling Units. Under normal operation this
field will read:
Cooling Group Status : None
Cooling Unit Status : None
None will be replaced with Warning or Critical if an alarm condition exists.
P+
The APC operating system (AOS) is functioning properly.
N+ The network is functioning properly.
N? A BOOTP or DHCP request cycle is in progress.
N– The InRow RC failed to connect to the network.
N! Another device is using the IP address of the InRow RC.
A+ The application is functioning properly.
A– The application has a bad checksum.
A? The application is initializing.
A! The application is not compatible with the AOS.
If the AOS status is not P+, contact APC Worldwide Customer
Support, even if you can still access the InRow RC.