USER’S GUIDE
InRow RC ACRC100 Series
5
2. Connect the APC null-modem cable (APC part number 940-0103A) to the
selected port on the computer and to the serial port at the InRow RC (use the
DB-9 connector on the front of the electrical panel).
3. Run a terminal program (such as HyperTerminal) and configure the selected
port as follows:
•9600 bps
•8 data bits
•no parity
•1 stop bit
•no flow control
4. Press
ENTER on the computer, repeatedly if necessary, to display the User
Name prompt.
If you are unable to display the User Name prompt, verify the following:
•The serial port is not in use by another application.
•The terminal settings are correct as specified in step 3.
•The correct cable is being used as specified in step 2.
5. Switch the main breaker to
OFF. Wait one second. Switch the main breaker to
ON.
6. Press
ENTER as many times as necessary to redisplay the User Name prompt,
then use the default, apc, for the user name and password. (If you take longer
than 30 seconds to log on after the User Name prompt is redisplayed, you must
repeat step 5 and log on again.)
Do not touch components on the electrical panel, other than the
service port.
If you wait too long to return power to the InRow RC, you must repeat step
5.