USER’S GUIDE
InRow RC ACRC100 Series
7
Critical alarm
When red, this LED indicates that a critical alarm condition exists and requires your
immediate attention. An audible alarm beeps every 30 seconds. Press any function key
to silence the audible alarm.
Watchdog Features
Overview
To detect internal problems and recover from unanticipated inputs, the InRow RC uses
internal, system-wide watchdog mechanisms. When it reboots to recover from an
internal problem, a System: Warmstart event is recorded in the event log.
Network interface watchdog mechanism
The InRow RC implements internal watchdog mechanisms to protect itself from
becoming inaccessible over the network. For example, if the InRow RC does not
receive any network traffic for 9.5 minutes (either direct traffic, such as SNMP, or
broadcast traffic, such as an Address Resolution Protocol [ARP] request), it assumes
that there is a problem with its network interface and restarts.
Resetting the network timer
To ensure that the InRow RC does not restart if the network is quiet for 9.5 minutes, the
InRow RC attempts to contact the Default Gateway every 4.5 minutes. If the gateway is
present, it responds to the InRow RC, and that response restarts the 9.5-minute timer.
If your application does not require or have a gateway, specify the IP address of a
computer that is running on the network most of the time and is on the same subnet.
The network traffic of that computer will reset the 9.5-minute timer frequently enough to
prevent the InRow RC from restarting.